Heatcraft Walk-In Controller Codes: Beacon II, Smart, intelliGen

Identify your Heatcraft walk-in controller, look up its error and alarm codes from the official manuals, and learn which resets to leave alone.

Fix todayStaff checks + technicianUpdated September 24, 2026
Walk-in down right now?Keep the door shut, check the product temperature, thenfollow the first-hour plan

Quick answer

Heatcraft walk-ins use three main electronic controllers: Beacon II (codes like E1 and A1), the Smart Controller (text codes like BXSEN and BOXHI) and the current intelliGen (ER and AL codes with a green, yellow or red light bar). Errors usually mean a sensor or wiring fault; alarms mean box temperature, start-up or input problems. Record the code before any reset.

Heatcraft makes walk-in refrigeration under the Bohn, Larkin, Climate Control and Chandler names, and many of those systems use one of three Heatcraft electronic controllers. Each speaks its own code language. This page helps you tell them apart and read their codes straight from Heatcraft's manuals.

For general Heatcraft system troubleshooting (not controller codes), see the site's Heatcraft walk-in cooler troubleshooting guide. For what these controllers do, see Heatcraft smart systems.

Which Heatcraft controller do you have?

The controller is usually mounted on the evaporator (the fan-coil unit in the box) or on a remote display near the door. The code style is the quickest clue:

If the display shows…You likely haveManual
Short codes like E1, A1, and modes like Coo, dEF, drnBeacon IIH-IM-79G
Five-letter text such as BXSEN, BOXHI and "CALL FOR SERVICE"Smart ControllerH-IM-80F
A green, yellow or red light bar and codes like ER01, AL01, IN01intelliGen Refrigeration ControllerH-IM-iRC (IG-IWRC)

Confirm with the label on the controller or evaporator. If none of these match, your walk-in may use a third-party controller (see Dixell and Carel codes) or a mechanical thermostat.

Before you reset anything

A few rules protect both the equipment and your warranty:

  • Write down the code first, photograph the display, and note the box temperature from a separate thermometer.
  • Don't power-cycle to clear a lockout unless you understand why it tripped. On Beacon II, the A3 start-up failure alarm appears after 4 unsuccessful restarts and clears through Service mode or power cycling. Clearing it without fixing the cause just puts the compressor through more failed starts.
  • Don't reset compressor shutdown codes (Beacon II E7, Smart Controller SHTDN) more than the manual allows. They mean a high-pressure, low-pressure or oil pressure switch opened. See pressure controls.
  • Don't change setpoints or parameters to "fix" an alarm. Adjusting alarm limits or defrost settings hides the symptom.
  • Leave electrical covers closed. Heatcraft states that installation and maintenance are to be performed only by qualified personnel.

Safety: The evaporator and condensing unit contain line-voltage wiring and fans that can start without warning. Staff should read the display and check breaker and disconnect positions only.

Beacon II codes

Source: Heatcraft Beacon II manual H-IM-79G (Jun 2020), pp.12, 15, 17–18.

Beacon II errors

CodeMeaning (per manual)
E1Room temperature sensor shorted, open or not installed
E2Defrost temperature sensor
E3Suction temperature sensor
E4Suction pressure transducer
E5Outdoor temperature sensor shorted
E6Low superheat (during cooling)
E7Compressor shutdown (high or low pressure switch or oil pressure switch open)
E9Multi-in/multi-out wiring error

Beacon II alarms

CodeMeaning (per manual)How it clears
A1High box temperature: above the high alarm limit (ALH) for the alarm timeAutomatically
A2Low box temperature: below the low alarm limit (ALL)Automatically
A3System start-up failure, after 4 unsuccessful restartsService mode or power cycling
A4Input fault (box temperature, suction temperature or transducer open)When the sensor or transducer is replaced
(Power failure)Loss of power to the evaporator

Defaults worth knowing: the alarm time defaults to 60 minutes. The high alarm limit defaults to +50°F on air-defrost (cooler) systems and +5°F on electric-defrost (freezer) systems; the low limit defaults to +30°F and −15°F. So on a default cooler, A1 means the box has been above 50°F for an hour, well past the 41°F cold-holding limit in the FDA Food Code. Treat A1 as a product emergency, not just an equipment alarm. See food safety when a walk-in fails.

Display modes (normal, not faults): oFF, Coo (cooling), Pdn (pump-down), dEF (defrost), drn (draining), plus dLY, tSt and SEr (see the mode table in the manual), and Loc/UnL (locked/unlocked).

Other factory defaults from the manual: box setpoint 35°F (air defrost) or −10°F (electric defrost); defrosts 2 per day (air) or 4 per day (electric); defrost termination +45°F (air) or +60°F (electric); fail-safe 40 minutes (air) or 30 minutes (electric). After an electric defrost, the controller holds a 2-minute drain-down, then a refreeze with the fans off until suction reaches 28°F or 3 minutes pass. That fan delay is why the fans stay off briefly after defrost.

Smart Controller codes

Source: Heatcraft Smart Controller manual H-IM-80F (Jul 2017), pp.10–11.

Smart Controller errors

CodeMeaning (per manual)
BXSENRoom (box) sensor
DFSENDefrost sensor
STSENSuction temperature sensor
SPSENSuction pressure transducer
ODSENOutdoor sensor shorted
SUPLOSuperheat too low
SHTDNCompressor shutdown (high/low pressure or oil pressure; not on QRC systems)
+COMM+Communication wiring fault (OUT must go to IN)

Smart Controller alarms

CodeMeaning (per manual)
BOXHIBox too warm
BOXLOBox too cold
STRUPStart-up failure
INFLTInput fault
(Power failure)Loss of power

When an alarm is active, the display shows "CALL FOR SERVICE," the buzzer sounds and the controller's dry alarm contacts close. Those contacts are rated 125 VAC / 1 A and can be wired by a technician to a monitoring system. See walk-in temperature monitoring.

The Smart Controller's "Smart Defrost" programs 8 defrost opportunities per day, with a 55°F termination and a 60-minute fail-safe, so seeing defrost more often than on older timers is normal on this controller.

intelliGen codes

Source: Heatcraft intelliGen Refrigeration Controller manual (H-IM-iRC, Feb 2025), p.43.

Light bar: green = normal; yellow = an error somewhere on the system (the unit at fault flashes); red = an alarm (the unit at fault flashes).

intelliGen errors

CodeMeaning (per manual)
ER01Box Temp
ER02Coil Temp
ER03EV Suc Temp
ER04EV Suc Press
ER11Control Circuit (only if the condensing unit is wired)
ER13Spare I/O
ER14 / ER15Power Supply Low / High
ER16Low Superheat
ER18Aux Probe Temp
ER19Replace Battery
ER20Log Disrupted (printed as "R20" in the manual)
ER22UI Failure
ER23Board Comm
ER24Aux Temp Override
ER25 / ER26System Cxn Lost / EV Cxn Lost
ER27 / ER28High Humidity / Low Humidity
ER29Humidity Sensor
ER31LL Conn Lost
ER32A2L Early Warning
ER33A2L Sensor Fault
ER34A2L Service
ER35A2L Mitigation
ER36A2L Refrigerant Mismatch
ER37A2L Mitigation Controller Communication Loss

intelliGen alarms and information codes

CodeMeaning (per manual)
AL01 / AL02High Box Temp / Low Box Temp
AL03System Startup (only if the condensing unit is wired)
AL04Input Fault (from ER01, ER03 or ER04)
AL06Door Open
AL10 / AL11LL High / Low Box Temp
AL12A2L Override
IN01Too Many Defrosts (defrosts under 5 minutes, 8 in a row)
IN05Too Few Defrosts (time-terminated, 8 in a row)

The ER32–ER37 and AL12 codes relate to A2L (lower-flammability) refrigerants. If any A2L code appears with a leak warning, get people out of the box and follow refrigerant leak safety. IN05 means eight defrosts in a row ended on time rather than temperature, which often points to coil icing; see evaporator coil frozen.

Heatcraft notes intelliGen may be wired only to Heatcraft-designed condensing units.

What a technician will check

  • Sensor faults (E1–E5, BXSEN–ODSEN, ER01–ER04): wiring and the sensor itself. The intelliGen manual gives a check in 32°F ice water: the sensor should read about 32,650 Ω and is replaced if it is more than 1,000 Ω off. Technicians should confirm against the specific controller's table.
  • Power supply errors (ER14/ER15) or a blank or rebooting display: control voltage. The Beacon II and intelliGen boards may shut down below 18 VAC, and a 208-V supply requires moving the evaporator transformer tap.
  • Low superheat (E6, SUPLO, ER16): expansion valve, sensor placement and charge. Beacon II's default is 7°F at the evaporator, adjustable to keep 20°F to 30°F at the compressor. See expansion valve (TXV).
  • Compressor shutdown or start-up failures: pressure switches, condenser airflow, charge and electrical components.

Bring the code, the controller type and your temperature log to the call. See what to tell a refrigeration technician.

Frequently asked questions

Is Russell part of Heatcraft?
No. Russell is an HTPG brand in the Rheem family. Heatcraft is a Lennox company whose brands include Bohn, Larkin, Climate Control and Chandler. Russell EcoNet codes are on the controller alarm codes page.
What are Heatcraft's default box temperatures?
The Beacon II and Smart Controller manuals list factory defaults of 35°F for air-defrost (cooler) systems and −10°F for electric-defrost (freezer) systems. Your installer may have set different values.
Can I connect an intelliGen controller to any condensing unit?
No. Heatcraft's manual says intelliGen may be wired only to Heatcraft-designed condensing units.
Why does my Beacon II show dEF or drn?
Those are normal operating modes, not faults: dEF is defrost and drn is the drain-down period after defrost. The box air temperature can rise briefly during them.

About this guide

Written by a walk-in design and installation company, for the people who run them

JayComp Development has designed and built walk-in coolers, beer caves and refrigerated stores since 1996. This guide explains what goes wrong with a walk-in, what staff can safely check, and what to expect from a technician.

We don't run repair service calls. If your walk-in has failed, call a licensed commercial refrigeration technician. When repairs stop making sense, we design and install replacement walk-ins, refrigeration systems, panels and glass doors.